A battery is a vital element of
any battery-backed system. In many cases the battery is more
expensive than the system it is backing up. Hence we need to adopt
all practical measures to conserve battery life.
As per manufacturer's data sheets, a 12V rechargeable lead-acid
battery should be operated within 10. IV and 13.8V. When the
battery charges higher than 13.8V it is said to be overcharged,
and when it discharges below 10.IV it can be deeply discharged. A
single event of overcharge or deep discharge can bring down the
charge-holding capacity of a battery by 15 to 20 per cent.
It is therefore necessary for all concerned to monitor the charge
level of their batteries continuously. But, in practice, many of
the battery users are unable to do so because of non-availability
of reasonably-priced monitoring equipment. The circuit idea
presented here will fill this void by providing a circuit for
monitoring the charge level of lead-acid batteries continuously.
The circuit possesses two vital features:
First, it reduces the requirement of human attention by about 85
per cent.
Second, it is a highly accurate and sophisticated method.
Input from the battery under test is applied to LM3914 1C. This
applied voltage is ranked anywhere between 0 and 10, depending
upon its magnitude. The lower reference voltage of 10.IV is ranked
'0' and the upper voltage of 13.8V is ranked as '10.' (Outputs 9
and 10 are logically ORed in this circuit.) This calibration of
reference voltages is explained later.
1C 74LS147 is a decimal-to-BCD priority encoder which converts the
output of LM3914 into its BCD complement. The true BCD is obtained
by using the hex inverter 74LS04. This BCD output is displayed as
a decimal digit after conversion using IC5 (74LS247), which is a
BCD-to-seven-segment decoder/driver. The seven-segment LED display
(LTS-542) is used because it is easy to read compared to a bar
graph or, for that matter, an analogue meter. The charge status of
the battery can be quickly calculated from the display. For
instance, if the display shows 4, it means that the battery is
charged to 40 per cent of its maximum value of 13.8V.
The use of digital principles enables us to employ a buzzer that
sounds whenever there is an overcharge or deep discharge, or there
is a need to conserve battery charge. A buzzer is wired in the
circuit such that it sounds whenever battery-charge falls to ten
per cent. At this point it is recommended that unnecessary load be
switched off and the remaining charge be conserved for more
important purposes.
Another simple combinational logic circuit can also be designed
that will sound the buzzer when the display shows 9. Further
charging should be stopped at this point in order to prevent
overcharge.
The circuit is powered by the battery under test, via a voltage
regulator 1C. The circuit takes about 100 mA for its operation.
For calibrating the upper and lower reference levels, a digital
multimeter and a variable regulated power supply source are
required. For calibrating the lower reference voltage, follow the
steps given below:
Set the output of power supply source to 10. IV.
Connect the power supply source in place of the battery.
Now the display will show some reading. At this point vary preset
VR2 until the reading on the display just changes from 1 to 0.
The higher reference voltage is
calibrated similarly by setting the power supply to 13.8V and
varying preset VR1 until reading on the display just changes from
8 to 9.
|